Upon arrival found boiler on error code LOC 31 which refers to LOC 1 ignition failure, tried 3 times to ignite but it failed, upon testin flame sense signal, rpm on blower, and sequence of operations found all this within range, however upon testing gas pressure found that unit upon ignition and firing WC” gas pressure drop to 4.1 minimum require to operate boiler is 4” and this is only with boiler running, ga spressures drops too low, customer must have PSEG or gas provider adjust gas pressure to be increased a few WC” in order to provide proper gas pressure to unit.